A single-phase transformer has 500 turns on the primary and 40 turns
on the secondary winding. The mean length of the magnetic path in the
iron core is 150 cm and the joints are equivalent to an air-gap of 0.1
mm. When a voltage of 3000 V is applied to the primary, maximum flux
density is 1.2 Wb/m\(^2\).
Calculate
the cross-sectional area of the core
no-load secondary voltage
the no-load current drawn by the primary
power factor on no-load.
Given that AT/cm for a flux density of 1.2 Wb/m\(^2\) in iron to be 5, the corresponding
iron loss to be 2 watt/kg at 50 Hz and the density of iron as 7.8
gram/cm3.
\[\begin{aligned}
\text{AT per cm} &=5 \\
\text{AT for iron core} &=150 \times 5=750 \\
\text{AT for air-gap} & =H I=\frac{B}{\mu_{0}} \times l\\
&=\frac{1.2}{4 \pi \times 10^{-7}} \times 0.0001=95.5 \\
\text{Total AT for given}~ B_{\max }&=750+95.5=845.5 \\
\end{aligned}\]
the no-load current drawn by the primary
\[\begin{aligned}
\text{Max. value of }~I_{\mu} &=845.5 / 500=1.691 \mathrm{~A} \\
\text{r.m.s. value of}~ I_{\mu}&=1.691 / \sqrt{2}=1.196
\mathrm{~A}\\ \text{Volume of iron} &= \text{length}
\times \text{area}\\
& =150 \times 225=33.750 \mathrm{~cm}^{3} \\
\text{Density} &=7.8 \mathrm{gram} / \mathrm{cm}^{3} \\
\text{ Mass of iron} & =33,750 \times 7.8 / 1000=263.25
\mathrm{~kg}\\
\text{Total iron loss} &=263.25 \times 2=526.5 \mathrm{~W}\\
I_{w} & =526.5 / 3000=0.176 \mathrm{~A} \\
I_{0}&=\sqrt{I_{\mu}^{2}+I_{w}^{2}}=\sqrt{1.196^{2}+0.176^{2}}=0.208
\mathrm{~A}
\end{aligned}\]
\[\cos\phi_0
= I_w/I_0 = 0.176/1.208=0.1457\]
power factor on no-load.
Problem-4
A single-phase transformer has 1000 turns on the primary and 200
turns on the secondary. The no load current is 3 A at a power factor of
0.2 lagging. Calculate the primary current and power factor when the
secondary current is 280 A at a power factor of 0.80 lagging.
lags
behind the supply voltage by an angle of Thus \(V_{2}\)
Problem-5
A single-phase transformer with a ratio of 440/110 V takes a no-load
current of 5 A at 0.2 power factor lagging. If the secondary supplies a
current of 120 A at a power factor of 0.8 lagging, estimate the current
taken by the primary.
A transformer has a primary winding of 800 turns and a secondary
winding of 200 turns. When the load current on the secondary is 80 A at
0.8 power factor lagging, the primary current is 25 A at 0.707 power
factor lagging. Determine graphically the no-load current of the
transformer and its phase with respect to the voltage.
A single-phase transformer takes 10 A on no-load at power factor of
0.2 lagging. The turns ratio is 4:1 (step down). If the load on the
secondary is 200 A at a power factor of 0.85 lagging. Find the primary
current and power factor. Neglect the voltage-drop in the winding.