Set 4 — Reactance and Impedance Diagrams
Twenty worked problems on the drawing that every later calculation starts from. A single-line diagram is a picture of plant; a reactance diagram is a circuit. Getting from one to the other means choosing bases, propagating them through every transformer, converting each machine and line to per-unit, and then — because the ideal transformers have vanished — treating the whole thing as one ordinary series-parallel network. The last third of the set does exactly that and reduces it to a fault.
One base MVA, one base kV per zone. Transformers divide the system into zones; the base MVA is common to all of them and the base kV changes at each transformer in that transformer's own nameplate ratio. Set the bases first, before converting a single element.
Every element is converted by the same two rules. An impedance quoted in ohms is divided by \(Z_B = \text{kV}_B^2/\text{MVA}_B\) of its own zone. An impedance quoted in per-unit on its own rating is moved with \(X_{pu}^{\text{new}} = X_{pu}^{\text{old}}(\text{MVA}_{new}/\text{MVA}_{old})(\text{kV}_{old}/\text{kV}_{new})^2\).
The transformer disappears; the machine may not. A transformer whose nameplate ratio matches the ratio of the zone bases contributes only its impedance. A machine whose rated voltage differs from its zone's base voltage picks up a genuine \((\text{kV}_{old}/\text{kV}_{new})^2\) factor — that is not an error, it is the machine being described at other than its rated voltage.
Reactance diagram or impedance diagram? The impedance diagram keeps \(R\); the reactance diagram discards it, along with magnetising branches and static loads. For fault studies the discard is justified because \(X \gg R\) in transmission plant and the error is second-order — Problem 16 quantifies it. For load flow and loss calculation it is not justified at all.
Once converted, it is only a circuit. Series and parallel combination, delta–star conversion and Thévenin's theorem all apply unchanged. The whole point of the per-unit conversion was to earn the right to say that.
Reduce towards the fault, not away from it. Collapse the network to a single Thévenin reactance seen from the faulted bus with all emfs set to \(1.0\angle0^\circ\). Then \(I_f = 1/X_{th}\) per-unit and \(\text{MVA}_{sc} = \text{MVA}_B/X_{th}\).
Motors are sources during a fault. A synchronous or induction motor near the fault feeds current into it from its own stored magnetic energy and rotating inertia. Omitting motor contribution understates the fault duty, sometimes badly — Problem 19 finds it more than triples the current.
A transmission line of reactance \(j40\ \Omega\) operates at 138 kV. Taking a base of 50 MVA, find the base impedance of that zone and the per-unit reactance of the line.
Base impedance of the 138 kV zone:
The line reactance is quoted in ohms, so it is simply divided by the base of its own zone:
A sanity check against the bands of Set 3: a transmission line on a 50 MVA base should land somewhere between roughly 0.02 and 0.5 p.u. At 0.105 this one is comfortably inside, so no base error is indicated.
A 50 Hz system has the following element reactances, each measured in ohms in its own zone. Draw the reactance diagram on a base of 30 MVA and 33 kV in the transmission zone, the generator zones being at 11 kV, 6.2 kV and 6.2 kV respectively.
- Transmission line: \(20.5\ \Omega\) at 33 kV
- Transformer \(T_1\): \(15.2\ \Omega\) referred to 33 kV
- Transformer \(T_2\): \(16\ \Omega\) referred to 33 kV
- Generator \(G_1\): \(1.6\ \Omega\) at 11 kV
- Generator \(G_2\): \(1.2\ \Omega\) at 6.2 kV
- Generator \(G_3\): \(0.56\ \Omega\) at 6.2 kV
Everything here is in ohms, so every element uses the same relation with the base impedance of its own zone. Writing it once in the convenient rearranged form:
In this arrangement the base MVA multiplies and the base kV squared divides — worth writing out once and reusing, since six conversions follow.
Transmission zone, \(\text{kV}_B = 33\), so \(\text{kV}_B^2 = 1089\):
Generator \(G_1\), whose zone is at 11 kV so \(\text{kV}_B^2 = 121\):
Generators \(G_2\) and \(G_3\), whose zone is at 6.2 kV so \(\text{kV}_B^2 = 38.44\):
The reactance diagram is then six reactances of these values, connected in the topology of the single-line diagram, with each generator behind its own reactance driving \(1.0\angle0^\circ\) and all transformer symbols erased.
A base of 50 MVA, 138 kV is declared in the transmission zone of the system below. Find the base voltage in every other zone.
- \(T_1\): 20 MVA, 138/20 kV, feeding generator \(G_1\)
- \(T_2\): 20 MVA, 138/20 kV, feeding generator \(G_2\)
- \(T_5\): 15 MVA, 138/13.8 kV, feeding a synchronous motor
The base MVA is 50 everywhere — it does not change at a transformer and it does not change anywhere else. Only the base voltage moves, and it moves in the transformer's nameplate ratio:
Through \(T_1\) and \(T_2\), both 138/20 kV:
Through \(T_5\), 138/13.8 kV:
So the four zones are:
Note that the generators are rated at 18 kV, not 20. Their zone base is nevertheless 20 kV, because the base is set by the transformer, never by the machine. That mismatch is genuine and is dealt with in Problem 5.
Transformer \(T_1\) of Problem 3 is rated 20 MVA, 138/20 kV with \(X = 0.10\) p.u. on its own rating. Find its reactance on the 50 MVA, 138 kV base.
Apply the base-change formula. Working on the LT side, where the zone base is 20 kV and the transformer's own rating is also 20 kV:
Substituting:
Working on the HT side instead must give the same answer, and does — the base there is 138 kV and the rating is also 138 kV:
Generator \(G_1\) is rated 20 MVA, 18 kV with \(X'' = 0.20\) p.u. on its own rating, and sits in a zone whose base is 50 MVA, 20 kV. Find its reactance on the system base, and explain why the voltage factor is not unity here when it was in Problem 4.
The machine's own base is 20 MVA and 18 kV; the zone base is 50 MVA and 20 kV. Both factors act:
Evaluating each factor separately, since this is where sign and direction errors occur:
Why the factor is not unity. The zone base of 20 kV was fixed by transformer \(T_1\), whose LT winding is rated 20 kV. The generator connected to that winding happens to be an 18 kV machine. Nothing is wrong with either: an 18 kV generator feeding a transformer wound for 20 kV simply operates its transformer below nominal voltage, which is entirely ordinary.
Confirming through ohms, which must be invariant. On its own base \(Z_B = 18^2/20 = 16.2\ \Omega\), so \(X'' = 0.20(16.2) = 3.24\ \Omega\). On the zone base \(Z_B = 20^2/50 = 8.0\ \Omega\):
The system of Problem 3 contains a \(j40\ \Omega\) line and a \(j20\ \Omega\) line, both in the 138 kV zone. Find the per-unit reactance of each on the 50 MVA base, and state what happens if two line sections of equal ohmic reactance sit in zones of the same base voltage.
Both lines occupy the same zone, so both use \(Z_B = 380.88\ \Omega\) from Problem 1:
The two are in the ratio 2:1, exactly as their ohmic values are — dividing both by the same base preserves ratios.
Hence the general statement: two sections of equal ohmic reactance lying in zones of the same base voltage have identical per-unit reactance, and need only be computed once.
A synchronous motor rated 30 MVA, 13.8 kV with \(X'' = 0.20\) p.u. is fed through transformer \(T_5\) rated 15 MVA, 138/13.8 kV with \(X = 0.10\) p.u. Find both reactances on the 50 MVA, 138 kV base.
From Problem 3 the motor zone base is 13.8 kV, which matches both the motor's rating and the transformer's LT rating. Every voltage factor will therefore be unity and only the MVA ratios act.
Transformer \(T_5\), rated 15 MVA:
Motor, rated 30 MVA:
The two happen to be equal, which is a coincidence of the ratings rather than anything structural: the transformer is half the motor's MVA but has half its per-unit reactance to start with.
Assemble the complete reactance diagram of the system below on a base of 50 MVA, 138 kV, using the results of Problems 1 and 4 to 7. This system is used again in Problems 9, 13, 14, 15, 19 and 20.
- \(G_1\): 20 MVA, 18 kV, \(X'' = 0.20\) p.u. — \(T_1\): 20 MVA, 138/20 kV, \(X = 0.10\) — \(j40\ \Omega\) line
- \(G_2\): 20 MVA, 18 kV, \(X'' = 0.20\) p.u. — \(T_2\): 20 MVA, 138/20 kV, \(X = 0.10\) — \(j20\ \Omega\) line
- Motor: 30 MVA, 13.8 kV, \(X'' = 0.20\) p.u. — \(T_5\): 15 MVA, 138/13.8 kV, \(X = 0.10\)
Collecting every conversion already made, all on the 50 MVA base:
The diagram is now a single connected network with no transformers in it. Three sources, each an emf of \(1.0\angle0^\circ\) behind its own reactance, all referred to one common node:
Every element in each branch is simply in series, because the transformers that separated the voltage levels have been erased. That is the whole return on the per-unit conversion, and it is worth pausing on: a machine at 18 kV, a transformer, and a line at 138 kV have just been added together like three resistors.
Reduce the two generator branches of Problem 8 to a single reactance seen from the 138 kV bus.
Both generators drive the same bus through their own series chains, and both emfs are \(1.0\angle0^\circ\). Two equal sources in parallel behave as one source of the same emf behind the parallel combination of their reactances:
Evaluating:
A check worth making: the result must lie below the smaller of the two, and above half the smaller. Here \(0.354 < 0.366 < 0.7075\), so it does.
Distinguish the impedance diagram from the reactance diagram. State precisely what is discarded in passing from one to the other, and for which studies each discard is admissible.
The impedance diagram retains, for every element, the full series impedance \(R + jX\), together with the shunt branches — line charging capacitance and transformer magnetising admittance — and represents static loads by their impedances.
The reactance diagram discards, in this order:
Why each discard is admissible for fault studies. A fault collapses the voltage at the fault point, so the current is set by the source impedance alone. Every branch that was carrying a small current in proportion to the system voltage — magnetising, charging, load — now carries a current negligible against the fault current, which is set by a much smaller impedance. Discarding them changes the answer by well under one per cent.
Why resistance in particular may go. For transmission plant \(X/R\) runs from about 10 for a line to 30 or more for a large machine. The magnitude of \(R + jX\) exceeds \(X\) by \(\sqrt{1 + (R/X)^2}\), which at \(X/R = 10\) is 1.005 — a half per cent, and always in the direction of overstating the fault current, which is the safe direction for rating switchgear.
Where the discards are not admissible. Load flow needs resistance, since it determines the real power loss and the whole of the \(P\)–\(\delta\) relationship at distribution voltages. Loss and efficiency calculations obviously need it. Distribution networks with \(X/R\) near unity need it. And the d.c. offset and time constant of a fault current depend on \(X/R\) explicitly, so breaker duty calculations need it even though the symmetrical current does not.
A load of 30 MVA at 0.9 power factor lagging is connected at a 13.8 kV bus whose base is 50 MVA, 13.8 kV. Represent it as a shunt impedance on the impedance diagram, assuming the bus voltage is 1.0 p.u.
Express the load as a per-unit complex power:
The angle is \(\cos^{-1}(0.9) = 25.84^\circ\), positive because the load is lagging and therefore absorbing vars.
The shunt impedance that draws this power at 1.0 p.u. follows from \(S = V^2/Z^{*}\):
In rectangular form, which is what goes on the diagram:
Compare this with the source reactances of Problem 8, which run from 0.05 to 0.41 p.u. The load impedance is four to thirty times larger.
A delta-connected load of \((45 + j30)\ \Omega\) per phase is connected at a 13.8 kV bus. On a base of 50 MVA, 13.8 kV, find its per-unit impedance.
Per-unit impedance is a per-phase, star-referred quantity, so the delta must be converted first. For a balanced load:
Base impedance of the zone:
Hence:
Converting after dividing by \(Z_B\) would give \((45+j30)/3.809 = 11.81 + j7.88\) and then a division by 3 — the same answer, since both operations are scalings. Converting not at all gives three times too much and is the error to guard against.
The \(j40\ \Omega\) and \(j20\ \Omega\) lines are now connected between the same pair of 138 kV buses, in parallel. Find the combined per-unit reactance, and verify the result in ohms.
From Problem 6 the two per-unit values are 0.105 and 0.0525. In parallel:
Verifying in ohms — combine first, convert second:
The two routes agree because both lines lie in the same zone and therefore share a base impedance. Had they been at different voltage levels the ohmic combination would have been meaningless, while the per-unit one would still have been correct.
For the system of Problem 8, find the Thévenin reactance seen from the motor's 13.8 kV terminals, (a) with the motor omitted and (b) with the motor included as a source.
aMotor omitted. Looking back from the motor terminals, the path is \(T_5\) in series with the two generator branches in parallel. From Problem 9 the latter is 0.366:
bMotor included. The motor is itself an emf of \(1.0\angle0^\circ\) behind 0.333 p.u., connected directly at the terminals in question. Setting all emfs to zero to find the Thévenin impedance, its reactance appears in parallel with the system:
The motor has cut the Thévenin reactance by more than two thirds — from 0.700 to 0.226.
For the system of Problem 8, find the Thévenin reactance, fault MVA and symmetrical fault current for a three-phase fault on the 138 kV bus.
Seen from the 138 kV bus there are two paths: the two generators in parallel, and the motor through \(T_5\).
These two are in parallel at the faulted bus:
Fault MVA:
Base current at 138 kV, and hence the fault current:
Cross-check through the fault MVA:
A line has an impedance of \((8 + j40)\ \Omega\). Find the percentage error in fault current introduced by using the reactance alone, and repeat for elements of \(X/R = 3\) and \(X/R = 10\). State whether the error is on the safe side.
The true impedance magnitude, against the reactance alone:
Fault current is inversely proportional to impedance, so using \(X\) alone overstates it by
The general expression is worth extracting, since it makes the dependence explicit:
Evaluating at the two other ratios:
Direction of the error. Discarding \(R\) reduces the impedance, so the computed fault current is always larger than the true one. Switchgear selected on that figure is therefore over-rated rather than under-rated — the error is on the safe side.
A three-winding transformer has star-equivalent impedances \(Z_p = 0.02\), \(Z_s = 0.05\) and \(Z_t = 0.07\) p.u. on a base of 15 MVA, 66 kV. Convert these to a 50 MVA base and describe how the unit appears on the reactance diagram.
All three arms share the same base and the voltage bases are propagated through the transformer itself, so only the MVA ratio acts:
Applying it:
On the diagram the unit is a three-terminal star: a common internal node with \(Z_p\) running to the primary bus, \(Z_s\) to the secondary bus and \(Z_t\) to the tertiary bus. It is not a single series element and it cannot be drawn as one.
Checking that the pairwise impedances survive the conversion, as they must:
A transformer nominally 138/13.8 kV with \(X = 0.10\) p.u. is operated on a tap that makes its actual ratio 138/14.5 kV, while the zone bases remain 138 kV and 13.8 kV. Find the off-nominal ratio and show how the transformer must now be represented.
The bases stand in the ratio
while the transformer's actual ratio is \(138/14.5 = 9.517\). The condition of Set 3 Challenge C1 — bases in the turns ratio — is therefore violated, and the ideal transformer will not vanish.
Expressing the actual ratio in per-unit. With 1.0 p.u. (138 kV) applied to the primary, the secondary produces 14.5 kV, which on a 13.8 kV base is
The representation. The transformer becomes its ordinary series reactance of 0.10 p.u. in series with an ideal transformer of ratio \(1 : t = 1 : 1.0507\). The reactance still converts by the base-change formula as usual; the ideal transformer is what remains and it must be kept.
What it does: for a primary at 1.0 p.u. and no load, the secondary sits at 1.0507 p.u. rather than 1.0 — a 5.07% boost, which is exactly what the tap was moved to achieve.
The alternative is to redeclare the zone base as 14.5 kV so that the bases are in the turns ratio. That removes the ideal transformer but forces every other element in that zone onto an awkward base, and prevents comparison with any other 13.8 kV zone. It is almost never worth doing.
A three-phase fault occurs at the motor terminals of the system of Problem 8. Using superposition, find the fault current contributed separately by the motor and by the rest of the system, and hence the total. Comment on the consequence of omitting the motor.
Every source drives \(1.0\angle0^\circ\) into the same short circuit, so each contributes independently and the contributions add.
System contribution, through \(T_5\) and the two generator branches — the 0.700 p.u. of Problem 14(a):
Motor contribution, straight through its own sub-transient reactance onto the faulted bus:
Total:
Confirming against the Thévenin route of Problem 14(b):
The small discrepancy is rounding in \(X_{th}\) only.
Consequence of omission. Ignoring the motor gives 1.429 p.u. against a true 4.429 — an understatement by a factor of 3.1, or 68%.
Complete the study of the system of Problem 8: for the three-phase fault at the motor terminals, find the fault MVA and the fault current in amperes, broken down by contribution.
From Problem 14, the Thévenin reactance at the motor bus:
Fault MVA:
Base current in the 13.8 kV zone — note this is the zone of the fault, not of the base declaration:
Total fault current, from the 4.429 p.u. of Problem 19:
Broken down by source:
Cross-checking through the fault MVA:
Practice Problems
Work each on paper before opening the answer. The answer is given so you can check yourself; the method is deliberately not.
P1. Find the base impedance of a 220 kV zone on a 100 MVA base, and the per-unit reactance of a \(j75\ \Omega\) line in it.
Show answer
\(Z_B = 220^2/100 = 484\ \Omega\); \(X_{pu} = 75/484 = \mathbf{0.155}\) p.u.P2. A base of 100 MVA, 11 kV is set at a generator. A 11/220 kV transformer then feeds a 220/66 kV transformer. Give the base voltage in all three zones.
Show answer
\(\mathbf{11}\), \(\mathbf{220}\) and \(\mathbf{66}\) kV — base MVA stays at 100 throughout.P3. A 40 MVA, 11/132 kV transformer has \(X = 0.12\) p.u. Find its reactance on a 100 MVA base with bases of 11 and 132 kV.
Show answer
\(0.12(100/40)(1)^2 = \mathbf{0.30}\) p.u. The voltage factor is unity because the bases were propagated through this transformer.P4. A 25 MVA, 13.2 kV generator with \(X'' = 0.15\) p.u. sits in a zone whose base is 100 MVA, 13.8 kV. Find its reactance on the system base.
Show answer
\(0.15(100/25)(13.2/13.8)^2 = 0.15(4)(0.9149) = \mathbf{0.549}\) p.u.P5. Two generator branches of 0.5 and 0.3 p.u. feed a common bus, both emfs at \(1.0\angle0^\circ\). Find the Thévenin reactance at that bus and the fault MVA on a 100 MVA base.
Show answer
\((0.5)(0.3)/0.8 = \mathbf{0.1875}\) p.u.; \(100/0.1875 = \mathbf{533}\) MVA.P6. A delta load of \((30 + j40)\ \Omega\)/phase sits at 11 kV on a 50 MVA base. Find its per-unit impedance.
Show answer
\(Z_Y = 10 + j13.33\ \Omega\); \(Z_B = 121/50 = 2.42\ \Omega\); \(Z_{pu} = \mathbf{4.13 + j5.51}\) p.u.P7. A load of 20 MVA at 0.8 p.f. lagging sits on a 100 MVA base at 1.0 p.u. voltage. Find its shunt impedance in per-unit.
Show answer
\(S_{pu} = 0.2\angle36.87^\circ\); \(Z = 1/0.2\angle-36.87^\circ = 5\angle36.87^\circ = \mathbf{4 + j3}\) p.u.P8. An element has \(Z = 5 + j20\ \Omega\). What percentage error in fault current results from using \(X\) alone, and in which direction?
Show answer
\(\sqrt{1 + (1/4)^2} = 1.0308\), so \(\mathbf{3.08\%}\) overstated — the safe direction.P9. A motor of \(X'' = 0.25\) p.u. is connected at a bus whose system Thévenin reactance is 0.40 p.u. Find the fault current at that bus with and without the motor.
Show answer
Without: \(1/0.40 = 2.5\) p.u. With: \(2.5 + 1/0.25 = \mathbf{6.5}\) p.u. — the motor contributes more than the whole system.P10. A 66/11 kV transformer is tapped to give an actual ratio of 66/11.55 kV, with bases of 66 and 11 kV. Find the off-nominal ratio.
Show answer
\(t = 11.55/11 = \mathbf{1.05}\) — a 5% boost, represented by an ideal transformer \(1{:}1.05\) in series with the impedance.P11. Two identical lines of \(j0.18\) p.u. run in parallel between two buses. One is switched out. By what factor does the transfer reactance change, and what does that do to the steady-state stability limit \(P = EV\sin\delta/X\)?
Show answer
From 0.09 to 0.18 — a doubling, which halves the stability limit. This is why a double-circuit outage is a far more serious contingency than a single one.P12. A three-winding transformer has \(Z_p = 0.04\), \(Z_s = -0.01\), \(Z_t = 0.09\) p.u. Is the negative arm an error?
Show answer
No. Only the pairwise sums are physical: \(Z_{ps} = 0.03\), \(Z_{pt} = 0.13\), \(Z_{st} = 0.08\) — all positive. The star node is a computational fiction.
Challenge Problems
Each of these needs an idea rather than a formula. Decide what the governing principle is before opening the answer.
C1. The reactance diagram sets every generator emf to \(1.0\angle0^\circ\). Examine this assumption: when is it exact, what does it cost when it is not, and how would you correct a fault calculation for a heavily loaded pre-fault system?
Show answer
When exact: only if the system was unloaded before the fault, so no current flowed and every internal emf equalled the terminal voltage, which the flat profile puts at 1.0 p.u.
What it costs otherwise: two separate errors. First, the internal emf of a loaded generator is not 1.0 — for a machine delivering \(S\) at terminal voltage \(V\), \(E = V + jX''I\), which for a lagging load makes \(|E| > 1\) and understates the fault current. Second, the emfs are not all at the same angle: power transfer requires angular separation, so the sources are genuinely out of step with one another and the simple parallel combination of Problem 9 is not exactly right.
The correction — superposition. The rigorous method treats the fault as the superposition of two states: (i) the pre-fault load flow, with its actual voltages and currents; and (ii) a "pure fault" network in which all sources are dead and a single source of \(-V_f\), the pre-fault voltage at the fault point, is applied there. The true post-fault current in any branch is the sum of the two. This is exactly the Thévenin construction, and it is why the \(Z\)-bus of Set 18 is the natural tool — column \(k\) of \(Z_{\text{bus}}\) gives every branch's share of a fault at bus \(k\) in one step.
Why the approximation survives in practice: pre-fault currents are typically 1 p.u. or less while fault currents are 5 to 20 p.u., so the superposed load component shifts the answer by a few per cent — and standards apply a voltage factor (commonly 1.1) that deliberately covers it, in the conservative direction.C2. Problem 15 found the 138 kV bus at 0.236 p.u. and Problem 14 found the motor bus at 0.226 p.u., so the lower-voltage bus is the more severely stressed. Explain why this is not paradoxical, and identify what network features generally make a bus a fault-level hot spot.
Show answer
Why not paradoxical: fault level in MVA and fault current in amperes are different quantities. Here \(\text{MVA}_{sc}\) is 211.5 at the 138 kV bus and 221.4 at the motor bus — genuinely higher at the motor. But the current differs far more dramatically, 885 A against 9265 A, simply because the base current at 13.8 kV is ten times that at 138 kV. Low-voltage buses always carry larger fault currents for the same fault MVA, and it is current that switchgear must interrupt and busbars must withstand mechanically.
What makes a hot spot:
— Rotating plant connected directly, with no intervening impedance. The motor's 0.333 p.u. sat straight across its bus while the generators reached it only through 0.700.
— Many parallel infeeds. Each added source lowers the Thévenin reactance; a strongly meshed bus is a strong bus in the stability sense and a difficult one in the switchgear sense.
— Low transformer impedance upstream. As Set 3 Problem 6 showed, halving the transformer impedance doubles the fault level below it.
— Low voltage. Purely arithmetic, but it dominates: the same MVA at a tenth the voltage is ten times the current.
The practical consequence is that industrial and generator-terminal buses, not transmission buses, usually set the switchgear specification — and that fault level must be recomputed from every bus, since no single reduction answers the question for all of them.C3. A colleague argues that since the per-unit system eliminates transformers, one could equally analyse the system in ohms referred to a single voltage level, and that per-unit therefore offers convenience but no new capability. Assess this claim carefully.
Show answer
The claim is technically correct and practically wrong, and it is worth being precise about which is which.
Correct: referring every impedance to one chosen voltage level by \(Z' = a^2Z\) does produce a single connected network in ohms, and it gives identical answers. Nothing in per-unit is mathematically unavailable in ohms. This was in fact how calculations were done before the 1920s.
Where the convenience becomes capability:
— Error detection. Per-unit values fall in narrow, memorable bands — machines near 0.15, transformers 0.05–0.15, lines 0.05–0.5. An impedance in ohms carries no such signal; 40 \(\Omega\) is unremarkable at 138 kV and absurd at 13.8. Set 3 Problem 14 showed a base error of a factor of 16 passing silently, and the only thing that catches it is the band.
— Manufacturer data. Nameplates quote per-unit or percent. Working in ohms means converting every one of them in and back out again, adding conversions rather than removing them.
— Scale independence. A 10 MVA and a 1000 MVA machine have nearly the same per-unit reactance, so intuition transfers between systems. In ohms they differ by a factor of a hundred and no intuition survives.
— Numerical conditioning. A load-flow Jacobian assembled in ohms across three voltage levels spans several orders of magnitude and conditions badly. In per-unit every entry is order unity — which for an iterative solver on a large network is the difference between convergence and failure, and is a genuine capability rather than a convenience.
— The \(\sqrt3\) cancels by construction (Set 3 Problem 16), so a stray one is a reliable error flag. In ohms there is no such flag.
Verdict: for a two-bus hand calculation the colleague is right and per-unit is merely tidy. For a 2000-bus network solved iteratively, the conditioning argument alone makes it indispensable — and the error-detection argument makes it indispensable even by hand.
Multiple-Choice Questions
MCQ 1. In a reactance diagram the base MVA:
(a) changes at every transformer (b) is common to the whole network (c) equals each machine's rating (d) changes at every voltage levelShow answer
(b). Only the base kV changes, and only at transformers, in the transformer's own ratio.MCQ 2. An impedance given in ohms is converted to per-unit by dividing by:
(a) the base MVA (b) \(Z_B\) of the declared zone (c) \(Z_B\) of its own zone (d) the base currentShow answer
(c). Using the declared zone's \(Z_B\) everywhere is the error that Problem 2 is built to expose.MCQ 3. A generator rated 18 kV sits in a zone whose base is 20 kV. Its per-unit reactance on the system base includes a factor of:
(a) \(18/20\) (b) \(20/18\) (c) \((18/20)^2\) (d) \((20/18)^2\)Show answer
(c). Old base voltage over new, squared — Problem 5.MCQ 4. A transformer whose nameplate ratio equals the ratio of its two zone bases contributes to the diagram:
(a) its impedance only (b) its impedance and an ideal transformer (c) an ideal transformer only (d) nothingShow answer
(a). The ideal transformer vanishes precisely when the bases stand in the turns ratio.MCQ 5. A delta-connected impedance of \(Z_\Delta\) per phase enters the diagram as:
(a) \(Z_\Delta/Z_B\) (b) \(Z_\Delta/(3Z_B)\) (c) \(3Z_\Delta/Z_B\) (d) \(Z_\Delta/(\sqrt3 Z_B)\)Show answer
(b). Convert delta to star first — per-unit quantities are always per phase and star-referred.MCQ 6. Passing from an impedance diagram to a reactance diagram discards:
(a) resistance only (b) resistance and shunt branches (c) resistance, shunt branches and static loads (d) nothing of consequenceShow answer
(c). All three, each justified by a specific inequality that holds during a fault — Problem 10.MCQ 7. Neglecting resistance in a fault calculation makes the computed current:
(a) too small (b) too large (c) unchanged (d) either, depending on \(X/R\)Show answer
(b) too large, since \(X < |Z|\) always. This is the safe direction for rating switchgear.MCQ 8. Two sources of equal emf may be replaced by one source behind the parallel combination of their reactances because:
(a) their reactances are equal (b) no current circulates between them (c) the network is linear (d) the fault is symmetricalShow answer
(b). Unequal emfs would circulate current and require Millman's theorem instead — Problem 9.MCQ 9. A synchronous motor during a nearby three-phase fault:
(a) draws no current (b) draws its normal load current (c) feeds current into the fault (d) may be ignoredShow answer
(c). Its rotor flux and inertia make it a source. Problem 19 finds it contributing more than the entire rest of the system.MCQ 10. The star arms of a three-winding transformer equivalent:
(a) are always positive (b) correspond to physical windings (c) may be negative, which is normal (d) are equal to one anotherShow answer
(c). Only the pairwise sums are measurable and constrained positive.MCQ 11. An off-nominal tap ratio appears on the diagram as:
(a) a modified impedance (b) an ideal transformer \(1{:}t\) in series with the impedance (c) a shunt branch (d) nothing, since per-unit removes itShow answer
(b). Per-unit removes the nominal ratio; the deviation from nominal is real and is the control variable of voltage regulation.MCQ 12. Fault level is a property of:
(a) the system as a whole (b) the generators only (c) a particular bus (d) the base MVA chosenShow answer
(c) a particular bus. It must be recomputed by reducing the network afresh from each candidate location — Problems 14 and 15 differ for exactly this reason.
Key Formulas
| Quantity | Relation | Notes |
|---|---|---|
| Base impedance | \(Z_B = \text{kV}_B^2/\text{MVA}_B\) | Of the element's own zone |
| Ohms to p.u. | \(X_{pu} = X_\Omega\,\text{MVA}_B/\text{kV}_B^2\) | Convenient rearrangement |
| Base change | \(X_{pu}^{new} = X_{pu}^{old}\dfrac{\text{MVA}_{new}}{\text{MVA}_{old}}\left(\dfrac{\text{kV}_{old}}{\text{kV}_{new}}\right)^2\) | For nameplate p.u. values |
| Base kV propagation | \(\text{kV}_{B,LT} = \text{kV}_{B,HT}\times\dfrac{\text{LT rating}}{\text{HT rating}}\) | MVA base never changes |
| Delta to star | \(Z_Y = Z_\Delta/3\) | Before dividing by \(Z_B\) |
| Load as impedance | \(Z = |V|^2/S^{*}\) | Valid at the stated voltage only |
| Series branch | reactances add | Legitimate because transformers vanished |
| Parallel sources | \(X = X_1X_2/(X_1+X_2)\) | Only if the emfs are equal |
| Thévenin at a bus | all emfs shorted, look in | Recompute for every candidate bus |
| Fault current | \(I_f = 1/X_{th}\) p.u. | Flat pre-fault profile assumed |
| Fault MVA | \(\text{MVA}_{sc} = \text{MVA}_B/X_{th}\) | |
| Fault amperes | \(I_f = I_B/X_{th}\) | \(I_B\) of the faulted zone |
| Superposition | \(I_f = \sum_k 1/X_k\) | Each source contributes independently |
| Error from dropping \(R\) | \(|Z|/X = \sqrt{1 + (R/X)^2}\) | Overstates current — safe direction |
| Three-winding star | \(Z_p = \tfrac12(Z_{ps}+Z_{pt}-Z_{st})\) | Cyclic; arms may be negative |
| Off-nominal ratio | \(t = \dfrac{V_{2,\text{actual}}/V_{2,B}}{V_{1,\text{actual}}/V_{1,B}}\) | Ideal transformer \(1{:}t\) retained |
Common Mistakes
Dividing every ohmic value by the declared zone's \(Z_B\). Each element uses the base impedance of the zone it actually occupies. In Problem 2 this would misstate \(G_2\) by a factor of 28, silently.
Changing the base MVA somewhere in the network. It is one number for the whole system; only the base kV moves.
Suppressing the voltage factor for a machine whose rating is "close" to the base. An 18 kV machine on a 20 kV base carries a genuine factor of 0.81 — Problem 5.
Inverting the base-change formula. MVA the right way up, kV inverted and squared.
Dividing a delta impedance by \(Z_B\) without converting to star first. Gives three times too much — Problem 12.
Combining impedances in ohms across a zone boundary. Legitimate only within one zone; the whole point of per-unit is that the combination works across boundaries.
Collapsing sources of unequal emf by the parallel formula. Valid only under the flat-start assumption, which makes every emf \(1.0\angle0^\circ\) — Problem 9.
Omitting motors from a fault study. Problem 19 understates the fault current by 68% when the motor is left out.
Using the base current of the declared zone rather than the faulted zone. Problem 20 needs \(I_B\) at 13.8 kV, not at 138 kV — a factor of ten.
Assuming the highest-voltage bus has the highest fault duty. It rarely does. Fault level belongs to a bus and must be recomputed from each one.
Treating a negative three-winding star arm as an error. Only the pairwise sums are physical — Problem 17.
Carrying a reactance diagram into a load-flow or loss calculation. Without \(R\) the lines are lossless and the answer is meaningless — Problem 10.
The diagram assembled in Problem 8 and reduced in Problem 20 is the last one in this book that will be drawn by hand. Its elements came from nameplates and from ohmic values supplied in the question; nothing so far has said where those ohms come from.
Sets 5 to 8 answer that. The series reactance of a line follows from the geometry of the conductors and their spacing, the shunt capacitance from their diameter and height above ground, and the corona loss from the surface gradient those same dimensions produce. Sets 9 to 15 then ask what the line does with those parameters — how much voltage it drops, how much power it can carry, and at what point the lumped model of Problem 8 stops being adequate. From Set 16 the diagram returns, but as a matrix rather than a picture, and the hand reduction of Problem 9 becomes a matrix inversion.